UNS Dashboards — /uns/dashboards

The UNS dashboard is operational, not BI: it shows the current value, the trend and the state of the namespace assets, and every number leads to its origin — the message, the Transformer and its version, or the telemetry source and address. Values arrive live through the same channel as the Namespace Explorer; what can be tested on that channel is in UNS test.
Each person sees only what their UNS roles allow them to read (UNS access). A variable outside that scope shows as No access, without the value.
The screen is under UNS Manager › Dashboards and only shows up with the UNS module in the license. It is where dashboards are built; people who only view use Plant Dashboards.
The list
Each line carries the Name (which opens the dashboard), the Context — the scope and the node or asset type —, the number of Widgets and of active Wallboards, the Publishing status (Published, with All profiles or the number of profiles, or Draft) and who and when under Created and Updated. A dashboard whose node or type was removed shows no context, in amber.
The search looks up name, description or context, and the Panel scope filter separates anchored dashboards from templates. In the actions column, whoever can edit has:
| Action | What it does |
|---|---|
| Edit | Opens the editor |
| Wallboards | Generates and revokes the tokens that let a TV open the dashboard without login (below) |
| Export .json | Downloads the dashboard as a portable file |
| Delete | Asks for confirmation. The dashboard’s wallboard tokens stop working |
Only whoever created the dashboard or an administrator edits, exports and deletes. The others only open it.
Export and import
The exported .json keeps references by name: the node path, the variable topic, the asset type
and the attribute, and the Application code of the limit sources. That is why it works for taking a
dashboard from one environment to another with the same Asset Model. A topic the exporter cannot read
comes out empty.
Import reads the file and looks up each reference in the local Asset Model. If any is missing, nothing is created and the message lists what is missing (“This Asset Model is missing: …”). If a dashboard with the same name already exists, the screen asks for another name for the copy.
The two scopes
Every dashboard has a scope, chosen in the dashboard properties:
| Scope | How it works |
|---|---|
| Anchored on a node | The dashboard belongs to a node of the namespace (a line, a machine). The widgets point to variables of the chosen node and of the nodes below it |
| Asset type template | The dashboard is designed once, by attribute of the asset type, and serves every instance of the type. The instance is chosen on screen, in the Instance picker, or fixed in the link with ?no= |
In a template, the editor asks for a Preview instance only to show real data while building; it is not stored in the dashboard. Types and attributes come from the Asset Model.
When the dashboard opens with no data, the screen says why: the anchor node or the type was removed from the Asset Model, no instance of the type is within your reach, the requested instance does not exist, or your roles do not reach any variable of the dashboard.
The screen format
| Format | What for |
|---|---|
| Free (scrolling) | The height grows with the widgets and the page scrolls. Good for desk analysis |
| TV 16:9 | Fixed 12-row screen, no scrolling: what fits here is what the TV shows |
| Monitor 16:10 | Fixed 13-row screen, no scrolling, in the 16:10 monitor ratio |
The grid always has 24 columns. On a phone, the widgets become a single column, in reading order (top to bottom, left to right).
Publishing

The Publishing section, in the Dashboard properties (click outside the widgets), decides whether the dashboard leaves the UNS Manager:
| Field | What it means |
|---|---|
| Publish to Plant Dashboards | On, the dashboard shows up in Plant Dashboards, for people who only view. Off, it is a Draft and stays here |
| Visible to | The profiles that see the published dashboard. None selected = everyone with the Plant Dashboards Tool |
Values are still limited by the viewer’s UNS roles. Below the section, Created by and Changed by show who touched the dashboard and when.
The editor

New dashboard and Edit open the editor in three columns:
- On the left, the variables to create widgets and the Widgets palette.
- In the center, the canvas in the chosen format, with the 24-column grid and the draft’s real data, before saving.
- On the right, the Properties of the selected widget or, clicking outside the widgets, those of the Dashboard (name, description, format, scope, node or type).
Placing widgets on the canvas
- From the palette: drag a widget onto the canvas, or click it to place it in the first free spot.
- From the variables: on an anchored dashboard, Add variable… opens the popup with the node’s variables (browse by branch, filter by type, only with value). Choosing one creates the widget for the data type, and then you just drag it on the canvas. On a template, the Type attributes list drags straight onto the canvas.
The widget created from a variable follows the data type:
| Data | Widget created |
|---|---|
| Boolean | State lamp |
| Historized text | State timeline |
| Non-historized text | State lamp |
| Historized number | Trend |
| Non-historized number | Current value |
Before the dashboard’s node (or type) is chosen, the variables area only asks for that step. Does the node have more than 2 thousand readable variables? Only the first ones show up: anchor the dashboard on a lower node.
The dashboard accepts at most 40 widgets. If there is no free space on the canvas for the widget, shrink another one or change the format.
Move, resize, undo
Drag the widget to move it and pull the corner to resize it. The position can also be typed in Grid position (Column, Row, Width, Height). The top bar has Undo, Redo, Duplicate and Delete, and keeps up to 100 steps. Typing in the same field in a row counts as a single step.
| Shortcut | Does |
|---|---|
| Delete | Deletes the selected widget |
| Ctrl+D | Duplicates |
| Ctrl+Z / Ctrl+Y | Undo / redo |
| Arrows | Move |
| Shift+arrows | Resize |
| Ctrl+S | Saves |
| Esc | Clears the selection |
Shortcuts do not work while the cursor is in a text field.
Saving and previewing as screen
The bar shows Unsaved changes or Saved at with the time. A widget with nothing to show is marked in yellow on the canvas, with what is missing, and Save refuses while there is any: “N widget(s) still have nothing to show (marked in yellow). Complete them in the properties before saving.”
Preview as screen opens the dashboard at the format’s size, as the TV will show it. Open dashboard leaves the editor for the view, and Dashboards goes back to the list; with unsaved changes, both ask first.
New Children grid and Transactional events widgets only show data after the dashboard is saved (“Save the dashboard to see this widget.”).
Generate with AI

Generate with AI, in the top bar, opens a box next to the canvas, in place of the properties. Describe what you want to see (for example, “I want a dashboard that consolidates the daily production of fillers 1 and 2”) and click Generate dashboard.
- With widgets on the canvas, choose Add to the dashboard (the default) or Replace the dashboard. On an asset type template, the result always replaces.
- The result is a draft on the canvas. Nothing is stored until you click Save, and Undo returns to what was there.
- The AI receives only the names and types of the variables the requester can read, never the values.
- If it cannot build the dashboard, the screen says why (for example, an attribute that is not historized for a chart over time). Proposed widgets that could not be used are left out, and the box says how many.
The feature is turned on in Settings › AI, under UNS dashboard by AI.
The box at the top of the properties

When a widget is selected, the properties start with a box that says:
- what the widget is for, in one line;
- how to use it, with what it needs;
- Missing to show data: the list of what has not been filled in yet — the dashboard’s anchor node (or asset type), the variable or attribute, the expression and inputs, the text, the image. With everything filled in, the box becomes Ready: the widget has what it needs.
If what is missing is the anchor node (or the asset type), the box itself brings the picker to choose it right there. The choice applies to the whole dashboard: every widget uses that context.
On widgets that read history (Trend, Multi-series trend, State timeline, SPC chart, Downtime Pareto, MTBF / MTTR, Histogram + Cp/Cpk and Heat map), the box warns when the variable’s attribute does not have Historize on: a variable that is not historized cannot be used for charts over time, and the widget will stay empty. Turn the tick on in the attribute, in Asset Model › Asset types.
The widgets
There are 25 widget types.
Every widget has a Title; empty, it uses the attribute name. Single-variable widgets (Current value, Trend, State timeline, Gauge, Progress bar, State lamp and SPC chart) ask for the Variable on an anchored dashboard or the Attribute on a template.
Current value, Consolidated, Calculated indicator, OEE breakdown and Production vs target also have Value size (Small, Medium, Large, Extra large), the size of the highlighted number.
Current value
Current value of a variable, with unit and limits, the age of the value and the quality. Clicking the value opens See where the value came from: the message or the telemetry source that stored it.
- Unit and Decimal places: empty, the unit comes from the attribute.
- Minimum limit and Maximum limit: empty, the attribute’s limits apply. Outside them, the value turns red, with “above limit” or “below limit”.
Trend
Chart of the variable over time, read from the Historian. Asks for a numeric variable and the Period: 1 h, 6 h, 24 h or 7 days. The attribute must have Historize on.
The widget has the same chart as the Namespace Explorer’s Trend: the period summary strip (last, minimum, maximum, average and samples), the switch to a paginated table and Export Excel — see The table and Excel.
State timeline
Colored band of the states over time: each value becomes a band. Asks for a state variable (text or boolean) and the Period. It also reads the Historian.
Gauge
Needle on a scale. Asks for a numeric variable, the Scale minimum and the Scale maximum (0 and 100 when empty). The Minimum limit and Maximum limit paint the alarm bands on the arc.
Progress bar
Horizontal bar that fills from the scale minimum to the maximum, with the limit marks. Good for tank level and target percentage. Same fields as the Gauge.
State lamp
One color per value. In States, each line has Value, Color (Green, Yellow, Red, Blue,
Gray) and Label — for example, RODANDO green and PARADO red. A value not on the list stays
gray. With no state registered, true lights green and false stays gray. The color always comes with
the label next to it.
Transactional events
Asks for no variable: it lists the latest integration messages that wrote to the dashboard’s node — when, the Delivery, the Values and the message, with a link to it. Shows up to 50 events from the last 30 days. The result of each value shows next to it: applied, older than the current one, nonexistent variable, message rejected or partly applied. A Test Bench message comes marked.
Children grid
One card per child of the dashboard’s node (each machine on the line, for example). Each card shows the worst quality of everything below it and how many variables are not GOOD. With an attribute chosen in Attribute shown on each child (optional), it also shows its value. Clicking a card goes down one level; the path at the top goes back.
Rollup
Sum, average, minimum, maximum or count of an Attribute across all children of the node. Asks for the attribute, the Function and, optionally, the Decimal places. Only GOOD values count, and a boolean counts as 1/0. The footer says how many instances had a value and how many are outside your access scope.
Calculated indicator
An expression over other variables (OEE, yield…). In Inputs, each line is a variable with an
alias (a, b…); in Expression, write the calculation with the aliases, for example
a / b * 100.
The expression accepts numbers, the input names, + - * / %, comparisons, && || !, a ? b : c and
the functions min max abs round floor ceil sqrt pow clamp if. If an input in use has no value, the
result is empty. If any input is outside your access scope, the widget warns you. It accepts Minimum
limit and Maximum limit, like Current value.
Text
Fixed text: section title, notice or instruction. Choose the Size (Small, Medium, Large, Extra large) and the Alignment. It reads no data.
Image
Logo, floor plan or machine photo. Upload PNG, JPG, GIF, WebP or SVG up to 10 MB: the screen shrinks the photo to at most 1920 px and 300 KB before saving, and the image is kept inside the dashboard. An SVG above 300 KB is not shrunk; simplify the file or export it as PNG. In Fit, Fit whole shows the whole image and Fill (crops) takes the space by cropping the edges.
SPC chart

Statistical process control chart over a historized numeric variable. It uses the most recent numeric readings of GOOD quality from the Historian.
| Field | What it holds |
|---|---|
| Chart type | Individuals and moving range (I-MR) — one point per reading — or Averages and ranges (X̄-R) — one point per subgroup of consecutive readings |
| Subgroup size | X̄-R only: from 2 to 10 readings per point |
| Samples on the chart / Subgroups on the chart | How many points the chart shows: from 10 to 200 |
| Horizontal axis | Time of each sample (to compare with what happened in the plant) or Sample number |
| Nelson rules | Which of the eight rules mark a point as out of control. A new widget comes with the first three |
| Lower limit (LSL) and Upper limit (USL) | Optional: the specification limits. With them, the chart computes Cp and Cpk |
| Control limits | Recalculated on each reading, or frozen |
The eight rules:
| Rule | Marks the point when |
|---|---|
| R1 | Point beyond 3σ from the center line |
| R2 | 9 points in a row on the same side |
| R3 | 6 points in a row rising or falling |
| R4 | 14 points in a row alternating |
| R5 | 2 out of 3 points beyond 2σ, on the same side |
| R6 | 4 out of 5 points beyond 1σ, on the same side |
| R7 | 15 points in a row within 1σ |
| R8 | 8 points in a row outside 1σ, on both sides |
The control limits sit at ±3σ from the center line. In I-MR, σ comes from the average moving range; in
X̄-R, from the average range of the subgroups. Cp is (LSE − LIE) / 6σ; Cpk is the smaller of
(LSE − média) / 3σ and (média − LIE) / 3σ, and with a single limit it uses the side that exists.
Freezing the baseline. Unfrozen, the center line and σ are recalculated from the chart samples, and a process that drifts slowly drags the limits along. When the process is stable, use Freeze with current samples: the center line and σ stay fixed (the chart shows frozen limits) and new points are compared against them. Recalculate again undoes it. Changing the chart type or the subgroup size unfreezes.
In the view, the N point(s) out of control badge highlights and filters the marked points, by rule. With few readings, the chart says “Not enough samples to compute the limits”.
The chart can also become an alert: in the UNS Monitor, the SPC chart out of control rule evaluates a dashboard chart every minute.
Variable table
Several variables in a grid: the name, the value with its unit, the quality and how long ago it arrived. In Table rows, add up to 20 rows, each with the variable and, if you want, a name (empty, it uses the attribute); the arrows change the order. A value outside the variable’s range turns red. Clicking the row shows where the value came from.
OEE breakdown
Availability × Performance × Quality, with the target and the biggest loss. Pick the three variables, say in Variables come as whether they arrive as % (0 to 100) or Fraction (0 to 1) and enter the OEE target (%). OEE is the product of the three; below the target, it turns red. The Biggest loss line points to the factor pulling the result down the most.
Production vs target
Produced in the shift against the target. The variable is the shift counter, which resets at the changeover. Enter the Shift target and the Shift start times, each with its start time, in the dashboard’s time zone. The widget shows the percentage, a mark on the bar where production should be, the Expected by now, the Current rate, the Required rate and the Forecast at shift end.
Multi-series trend
Up to 6 variables on the same chart, to compare. All in the same unit: the chart has a single axis. For different quantities, use one Trend widget for each. In Series, add one row per variable, with an optional name, and choose the Period. Reads the Historian.
Downtime Pareto
Time in each machine state over the period, from largest to smallest, with the cumulative share. It asks
for a historized state variable (text, such as PARADA_FALTA_MATERIAL), the Period and, in States
that are not downtime, the values left out of the count, separated by commas and written as they arrive
in the variable (for example, RODANDO, SETUP).
MTBF / MTTR
Mean time between failures and mean time to repair, with the availability and the number of failures in
the period, from a historized state variable. In Running states, say which values count as the machine
running (for example, RODANDO). Failure states (optional): with nothing here, every stop counts as a
failure; with the list, planned stops (setup, lunch) stay out.
Histogram + Cp/Cpk
Distribution of the samples over the period, with process capability. It asks for a historized numeric variable, the Period, the Bins (bars) and, if any, the specification limits LSL and USL, which also accept a source. Cp/Cpk use the short-term σ (moving range); Pp/Ppk use the overall σ. The index turns green from 1.33. With too many samples in the period, the widget uses only part of them and says so.
Heat map
The average of each hour over the last 7, 14 or 30 days (Period field): rows are days, columns are hours. It helps find shift and time-of-day patterns. It asks for a historized numeric variable. The color goes from light to strong by the 5th to 95th percentiles of the period, so an isolated spike does not wash out the rest. An hour with no data stays empty.
Active alarms
The rules in alert now that reach the dashboard’s node, with the value, the threshold and the acknowledgement. It includes rules whose topic filter reaches the node (UNS Manager › Alerts) and the SPC charts of this dashboard. Besides the title there is only one option: Include the general UNS rules (disk, connection, lag), which have no topic and apply to the whole UNS.
Shift and clock
Local time, the current shift and how long until it ends. Enter the Shift start times; the time follows the dashboard’s time zone. Good for TV.
Synoptic

A picture of the line or machine with live values where each sensor is. Upload the picture (same rules as the Image widget) and click Values, position and colors: the popup shows the picture and the list of values, with a search once the list grows.
- + Value adds an item, with a name and a variable.
- Pick an item and click the picture to place it there; the next one without a position is already selected. The points can also be dragged, and Remove clears the position.
- With the item selected, Limits and colors sets that value’s color ranges: condition, comparison value, color and label. The first matching rule applies; with no rule, the value keeps the normal color. In the Synoptic the color paints the value’s tag, and the range value is always a typed number (no source).
On a node dashboard, Place by flow uses the relationships between the node’s equipment (feeds, depends on…) to spread the values from left to right, one column per stage — equipment in parallel stays in the same column. A value of equipment outside the flow stays where it was, and Undo brings the positions back.
Map


The children of the dashboard’s node as points colored by status (the worst quality of everything below each one). In Map type:
| Type | How it works |
|---|---|
| Geographic | Uses the latitude and longitude registered on each node, over an outline built into the system: it works without internet, including on TV. With no child having coordinates, the widget asks for them |
| Floor plan | Uses a picture of the plant. Upload the picture and click Place on the floor plan: the popup is the same as the Synoptic’s, one point per child of the node |
Attribute shown on each child (optional) puts that attribute’s value next to the name.
To navigate: the + and − buttons zoom in and out, and the third returns to the original framing; dragging moves, double-click zooms in on the point and Ctrl + mouse wheel zooms. The legend alongside (below, on a narrow widget) sums up how many points are in each status and lists each one; clicking one zooms the map to it.
Color ranges

Current value, Calculated indicator, Consolidated, Gauge, Progress bar and Variable table have the Color ranges section, above Grid position. Each range is a rule: a condition on the value, a color and, optionally, a label shown next to the value (e.g. “Critical”).
| Condition | Matches when the value… |
|---|---|
| Greater than / Greater than or equal to | goes past the number (or reaches it) |
| Less than / Less than or equal to | stays below the number (or reaches it) |
| Between | is from one number to another, both inclusive |
| Outside | is below the first number or above the second |
| Equal to / Not equal to | is (or isn’t) that text or number — text is case-insensitive |
| Contains | has that piece of text (useful for states such as ALARM_TEMP) |
Order matters: the first matching range applies, top to bottom, and the arrows change the priority. The color is one of the five status colors or a Custom color, from the browser’s picker. When no range matches, the widget goes back to the usual behavior: red outside the Minimum limit and the Maximum limit.
Where the color shows:
| Widget | Effect |
|---|---|
| Current value, Calculated indicator, Consolidated | The number in the range color. In Apply color to, Whole card paints the widget background (text switches to black or white, whichever is readable) |
| Gauge | Ranges show in a light tone on the arc; the value arc and the number take the range color |
| Progress bar | Ranges show in a light tone on the track; the fill takes the range color |
| Variable table | Ranges apply to every row; Cell background paints the value cell |
A range value (and the end, in Between and Outside) can come from a source, like the limits: the selector next to the field switches Number to Global Variable, Application Variable or UNS variable — the set-point the MES publishes, for example. With a source, the typed number becomes the fallback and may stay empty; with no value in the source and no fallback, the range does not match. Text conditions do not take a source. See Limits with a source.
Generate with AI also builds ranges when the request mentions them (“green up to 80, yellow up to 95, red above”).
Limits with a source
In the limit fields — Minimum limit and Maximum limit (Current value, Calculated indicator, Gauge, Progress bar), Scale minimum and Scale maximum (Gauge and Bar) and LSL and USL (SPC chart and Histogram + Cp/Cpk) —, the picker next to the label chooses where the number comes from:
| Source | What it holds |
|---|---|
| Number | The typed number |
| Global Variable | A numeric Global Variable, chosen from the list with its current value next to it |
| Application Variable | An Application Variable: choose the Application and the variable |
| UNS variable | Another variable of the namespace, live (the machine setpoint, for example) |
With a source, the number typed in If the source has no numeric value, use becomes the fallback. A scale is only replaced by the source value if it stays valid (minimum lower than maximum). A source chosen halfway — without the variable or without the Application — marks the widget in yellow and prevents saving.
Unit
The Unit field is free text. The button next to it opens Units of measure: search by symbol or name (bar, flow, rpm…) and clicking copies the symbol into the field. It is not a registry: you can type another one.
Viewing the dashboard
Opening a dashboard shows the context path, the Live indicator and, on a template, the Instance picker. Full screen takes the whole screen; on a fixed-format dashboard (TV or Monitor), the grid fills the screen without scrolling. Edit shows up for whoever can edit.
Wallboard on the TV

To leave a dashboard on a TV with nobody logged in, generate a token in Wallboards, on the list:
| Field | What it holds |
|---|---|
| Description | To know later which TV uses the token (e.g. Line 1 TV) |
| Expires at | Optional. Empty, the token does not expire |
The token starts with cms_unsw_ and shows up only once, already inside the Wallboard URL
(/uns-wall?token=...): copy it right away. The TV sees only what you and the dashboard owner both
see. Revoke cuts it off at once, and Reactivate brings it back.
The tokens of all dashboards also show up in Wallboard and Monitoring › UNS dashboards, to follow and revoke them in one place. A new token can also be generated there, by choosing the dashboard.
How to put it on the TV
- Open the URL in the TV browser once. The token goes into the browser storage and leaves the address bar, so it does not leak in a photo of the screen.
- On a type template, add
?no=with the instance, or choose the instance on the screen itself. - Click TV mode: the screen goes full screen and the text grows with the TV width. Esc exits.
- In the bottom right corner, the A− / A+ control adjusts the size from 100% to 200%, and Auto goes back to sizing by width. The setting is saved in the TV browser and also applies to the UNS Monitor and the Applications Panel.
If the token is revoked, expires or is invalid, the TV shows UNS wallboard and asks for a new token, which can be pasted right there. A fixed-format dashboard fills the TV screen without scrolling.
The dashboard wallboard is different from the Monitor TV: the dashboard shows the data of a node, and the Monitor TV shows the health of the whole UNS.